Identification of Deformation Processes within Power Oil Transformers Using Maps of ADC Descriptors in Selected Frequency Bands
A. Olszewska
Department of Optoelectronics, Silesian University of Technology, B. Krzywoustego 2, 44-100 Gliwice, Poland
Full Text PDF
The paper presents identification results of deformation processes within power oil transformers where - according to dissolved gas analysis investigation results - partial discharges took place. The original method worked out for analysis of acoustic emission signals recorded within tested transformer and particularly maps of ADC descriptors have been applied. Analysis has been carried out within chosen frequency bands in order to distinguish signals coming from different sources (among other things partial discharges, Barkhausen's effect, circulation of the oil, and outer acoustic sources). One source of partial discharges has been identified within the tested transformer as a result of analysis of acoustic emission signals.

DOI: 10.12693/APhysPolA.124.525
PACS numbers: 43.40.Le, 52.80.-s, 43.60.-c, 43.58.Ta, 77.22.Jp, 84.70.+p